| Generator Specifications |
|
| Standby Output 150° Rise kVA/kW: |
|
| Single phase voltage @ 240V |
25/25 |
| 3 phase voltage @ 208V |
37/30 |
| 3 phase voltage @ 240V |
37/30 |
| 3 phase voltage @ 480V |
37/30 |
| Continuous Output 125° Rise kVA/kW: |
|
| Single phase voltage @ 240V |
22/22 |
| 3 phase voltage @ 208V |
33/27 |
| 3 phase voltage @ 240V |
33/27 |
| 3 phase voltage @ 480V |
33/27 |
| Amperage (Continuous) kVA/kW: |
|
| Single phase amperage @ 240V/120V |
91.7/2x91.7 |
| 3 phase amperage @ 208V |
91.6 |
| 3 phase amperage @ 240V |
79.4 |
| 3 phase amperage @ 480V |
39.7 |
| Voltage-3 phase adjustable |
208/220/240/416/440/460/480 |
| Voltage-Single phase adjustable |
120/127/139/240/254/277 |
| 3 phase power factor |
0.8 |
| Voltage regulation |
1/2% |
| Frequency |
60 Hertz |
| Total harmonic distortion |
< 5% |
| Insulation |
Class H |
| Engine Specifications |
|
| Manufacturer |
John Deere |
| Model |
4024TF270 |
| Cylinders |
4 |
| Induction system |
Turbocharged |
| Displacement, L (cu. in.) |
2.4L (149) |
| HP @ rated speed |
48 |
| RPM |
1800 |
| Bore and stroke |
3.4" x 4.1" |
| Lubrication capacity (with filter) |
8.5 Qts |
| Battery recommendation min.(cold cranking amps) |
675 |
| - Battery rack and cable supplied (battery not included) |
| - Spin-on oil filter |
| - Thermostat controlled cooling system |
| - 12V engine alternator |
| - 12V starter motor |
| Receptacle Specifications |
|
| 120 Volt 20 Amp GFCI |
2 |
| 120/240 Volt CS6369 Twistlock |
2 |
| Two wire remote start capability |
Yes |
| Fuel System Specifications |
|
| Fuel Consumption Standby Rating (GPH): |
|
| 1/2 load |
1.4 |
| Full load |
2.8 |
| Approximate Run Time Standby Rating (Hours): |
|
| 1/2 load |
36 |
| Full load |
18 |
| Fuel Capacity: |
|
| Fuel |
Diesel |
| Galllons |
50 |
| Weights and Dimensions |
|
| Weight without fuel |
3075 |
| Weight without fuel and without trailer |
2515 |
| Dimensions with trailer (L x W x H) |
131” x 62” x 72” |
| Dimensions without trailer (L x W x H) |
74” x 38” x 52” |
| Sound Level |
|
| Sound level dB(A) |
67 |
| 7 meters, full load |
|
| Engine, Generator Instrumentation |
|
| Voltmeter, ammeter, frequency meter, phase selector switch,
oil pressure gauge, water temperature gauge, battery voltmeter, start/stop/auto
switch, voltage adjusting rheostat, elapsed time meter, individual fault
shutdown lights, panel lights with switch, receptacle panel |