| Generator Specifications |
|
| Standby Output 150° Rise kVA/kW: |
|
| Single phase voltage @ 240V |
18/18 |
| 3 phase voltage @ 208V |
25/20 |
| 3 phase voltage @ 240V |
25/20 |
| 3 phase voltage @ 480V |
25/20 |
| Continuous Output 125° Rise kVA/kW: |
|
| Single phase voltage @ 240V |
18/18 |
| 3 phase voltage @ 208V |
23/18 |
| 3 phase voltage @ 240V |
23/18 |
| 3 phase voltage @ 480V |
23/18 |
| Amperage (Continuous) kVA/kW: |
|
| Single phase amperage @ 240V/120V |
75.0/150.0 |
| 3 phase amperage @ 208V |
62.5 |
| 3 phase amperage @ 240V |
54.1 |
| 3 phase amperage @ 480V |
27.1 |
| Voltage-3 phase adjustable |
208/220/240/416/440/460/480 |
| Voltage-Single phase adjustable |
120/127/139/240/254/277 |
| 3 phase power factor |
0.8 |
| Voltage regulation |
1/2% |
| Frequency |
50 or 60 Hertz |
| Total harmonic distortion |
< 5% |
| Insulation |
Class F |
| Engine Specifications |
|
| Manufacturer |
Isuzu |
| Model |
4LE |
| Cylinders |
4 |
| Induction system |
Naturally aspirated |
| Displacement, L (cu. in.) |
2.2L (133) |
| HP @ rated speed |
34.5 |
| RPM |
1800 |
| Bore and stroke |
3.34" x 3.78" |
| Lubrication capacity (with filter) |
8.6 Qts |
| Battery recommendation min.(cold cranking amps) |
750 |
| - Battery rack and cable supplied (battery not included) |
| - Spin-on oil filter |
| - Thermostat controlled cooling system |
| - 12V engine alternator |
| - 12V starter motor |
| Receptacle Specifications |
|
| 120 Volt 20 Amp GFCI |
4 |
| 120/240 Volt CS6369 Twistlock |
2 |
| Two wire remote start capability |
Yes |
| Fuel System Specifications |
|
| Fuel consumption (GPH): |
|
| 1/2 load |
1.3 |
| Full load |
2.0 |
| Fuel |
Diesel |
| Approximate run time (Hours): |
|
| 1/2 load |
38 |
| Full load |
25 |
| Fuel Capacity (Gal.) |
50 |
| Weights and Dimensions |
|
| Weight without fuel |
2265 |
| Weight without fuel and without trailer |
1790 |
| Dimensions with trailer (L x W x H) |
131" x 62" x 70" |
| Dimensions without trailer (L x W x H) |
74" x 38" x 52" |
| Sound Level |
|
| Sound level dB(A) |
64 |
| 7 meters, full load |
|
| Engine, Generator Instrumentation |
|
| Voltmeter, ammeter, frequency meter, phase selector switch,
oil pressure gauge, water temperature gauge, battery voltmeter, start/stop/auto
switch, voltage adjusting rheostat, elapsed time meter, individual fault
shutdown lights, panel lights with switch, receptacle panel |